Brand: CL
Model: DW-6195
Pictures are for reference only.
Technical Specifications:
Measurement Range:
Voltage Range: 10 to 600V
Voltage Resolution: 0.1V
Voltage Accuracy: ± (0.5% + 0.5V)
Current Range: 20A to 1200A
Current Resolution:
0.001A < 10A; 0.01A ≥10A
0.01A < 100A; 0.1A≥100A
0.1A< 1000A; 1A ≥1000A
Current Accuracy:
±(0.5% + 0.1A) up to 10A
± (0.5% + 0.5A) up to 100A
± (0.5% + 5A) up to 1000A
Power Factor Range: 0.00 to 1.00
Power Factor Resolution: 0.01
Power Factor Accuracy: ± 0.04
Phase Angle Range: -180° to 180°
Phase Angle Resolution: 0.1°
Phase Angle Accuracy: ± 1°
Frequency Range: 45 to 65Hz
Frequency Resolution: 0.1 Hz
Frequency Accuracy: 0.1 Hz
Active (Real) Power:
Range: 0.000 to 9.999 KW; Resolution: 0.001/0.01/0.1 KW; Accuracy: ± (1%+0.008 KW)
Range: 10.00 to 99.99 KW; Resolution: 0.01/0.1 KW; Accuracy: ± (1%+0.08 KW)
Range: 100.0 to 999.9 KW; Resolution: 0.1 KW; Accuracy: ± (1%+0.8 KW)
Range: 1.000 to 9.999 MW; Resolution: 0.001 MW; Accuracy: ± (1%+0.008 MW)
Apparent Power:
Range: 0.000 to 9.999 KVA; Resolution: 0.001/0.01/0.1 KVA; Accuracy: ± (1%+0.008 KVA)
Range: 10.00 to 99.99 KVA; Resolution: 0.01/0.1 KVA; Accuracy: ± (1%+0.08 KVA)
Range: 100.0 to 999.9 KVA; Resolution: 0.1 KVA; Accuracy: ± (1%+0.8 KVA)
Range: 1.000 to 9.999 MVA; Resolution: 0.001 MVA; Accuracy: ± (1%+0.008 MVA)
Reactive Power:
Range: 0.000 to 9.999 KVAR; Resolution: 0.001/0.01/0.1 KVAR; Accuracy: ± (1%+0.008 KVAR)
Range: 10.00 to 99.99 KVAR; Resolution: 0.01/0/0.1 KVAR; Accuracy: ± (1%+0.08 KVAR)
Range: 100.0 to 999.9 KVAR; Resolution: 0.1 KVAR; Accuracy: ± (1%+0.8 KVAR)
Range: 1.000 to 9.999 MVAR; Resolution: 0.001 MVAR; Accuracy: ± (1%+0.008 MVAR)
Watt Hour ( Active Power Hour):
Range: 0.000 to 9.999 KWH; Resolution: 0.001 KWH; Accuracy: ± (2%+0.008 KWH)
Range: 10.00 to 99.99 KWH; Resolution: 0.01 KWH; Accuracy: ± (2%+0.08 KWH)
Range: 100.0 to 999.9 KWH; Resolution: 0.1 KWH; Accuracy: ± (2%+0.8 KWH)
Range: 1.000 to 9.999 MWH; Resolution: 0.001 MWH; Accuracy: ± (2%+0.008 MWH)
VA Hour (Apparent Power Hour): SH
Range: 0.000 to 9.999 KVAH; Resolution: 0.001 KVAH; Accuracy: ± (2%+0.008 KVAH)
Range: 10.00 to 99.99 KVAH; Resolution: 0.01 KVAH; Accuracy: ± (2%+0.08 KVAH)
Range: 100.0 to 999.9 KVAH; Resolution: 0.1 KVAH; Accuracy: ± (2%+0.8 KVAH)
Range: 1.000 to 9.999 MVAH; Resolution: 0.001 MVAH; Accuracy: ± (2%+0.008 MVAH)
VAR Hour (Reactive Power Hour): QH
Range: 0.000 to 9.999 KVARH; Resolution: 0.001 KVARH; Accuracy: ± (2%+0.008 KVARH)
Range: 10.00 to 99.99 KVARH; Resolution: 0.01 KVARH; Accuracy: ± (2%+0.08 KVARH)
Range: 100.0 to 999.9 KVARH; Resolution: 0.1 KVARH; Accuracy: ± (2%+0.8 KVARH)
Range: 1.000 to 9.999 MVARH; Resolution: 0.001 MVARH; Accuracy: ± (2%+0.008 MVARH)
Voltage & Current are the True RMS value
Safety Standard: IEC 1010, CAT III 600V
Built-in clock and calendar, real time data record with SD memory card, sampling time set from 2 to 7200 seconds ,Custom one-chip of microprocessor LSI circuit
Wire connections: 1P/2W, 1P/3W, 3P/3W, 3P/4W ACV input impedance is 10 Mega ohms
Display:
LCD size: 81.4 x 61mm
Dot matrix (320×240 pixels) with back light
Come with 4 PCs Test Leads, 4 PCs Alligator clips, 3 PCs Clamp Probe, AC to DC 9V adapter, 2G SD memory card and Carrying bag (OEM by CL)
Reviews
There are no reviews yet.